30 C.F.R. § 75.1101-14   Installation of dry powder chemical systems.


Title 30 - Mineral Resources


Title 30: Mineral Resources
PART 75—MANDATORY SAFETY STANDARDS—UNDERGROUND COAL MINES
Subpart L—Fire Protection

Browse Previous |  Browse Next

§ 75.1101-14   Installation of dry powder chemical systems.

(a) Self-contained dry powder chemical systems shall be installed to protect each belt-drive, belt takeup, electrical-controls, gear reducing units and 50 feet of fire-resistant belt or 150 feet of non-fire-resistant belt adjacent to the belt drive.

(b) The fire-control components of each dry powder chemical system shall be a type approved by the Underwriters' Laboratories, Inc., or Factory Mutual Engineering Corp.

(c) The components of each dry powder chemical system shall be located so as to minimize the possibility of damage by roof fall or by the moving belt and its load.

Browse Previous |  Browse Next