30 C.F.R. § 77.801 Grounding resistors.
Title 30 - Mineral Resources
The grounding resistor, where required, shall be of the proper ohmic value to limit the voltage drop in the grounding circuit external to the resistor to not more than 100 volts under fault conditions. The grounding resistor shall be rated for maximum fault current continuously and insulated from ground for a voltage equal to the phase-to-phase voltage of the system.
Title 30: Mineral Resources
PART 77—MANDATORY SAFETY STANDARDS, SURFACE COAL MINES AND SURFACE WORK AREAS OF UNDERGROUND COAL MINES
Subpart I—Surface High-Voltage Distribution
§ 77.801 Grounding resistors.