30 C.F.R. § 56.13011   Air receiver tanks.


Title 30 - Mineral Resources


Title 30: Mineral Resources
PART 56—SAFETY AND HEALTH STANDARDS—SURFACE METAL AND NONMETAL MINES
Subpart L—Compressed Air and Boilers

Browse Previous |  Browse Next

§ 56.13011   Air receiver tanks.

Air receiver tanks shall be equipped with one or more automatic pressure-relief valves. The total relieving capacity of the relief valves shall prevent pressure from exceeding the maximum allowable working pressure in a receiver tank by not more than 10 percent. Air receiver tanks also shall be equipped with indicating pressure gauges which accurately measure the pressure within the air receiver tanks.

Browse Previous |  Browse Next