30 C.F.R. Subpart K—Electricity
Title 30 - Mineral Resources
Circuits shall be protected against excessive overloads by fuses or circuit breakers of the correct type and capacity. Electric equipment and circuits shall be provided with switches or other controls. Such switches or controls shall be of approved design and construction and shall be properly installed. Individual overload protection or short circuit protection shall be provided for the trailing cables of mobile equipment. Electrical conductors shall be of a sufficient size and current-carrying capacity to ensure that a rise in temperature resulting from normal operations will not damage the insulating materials. Electrical conductors exposed to mechanical damage shall be protected. Mobile equipment shall not run over power conductors, nor shall loads be dragged over power conductors, unless the conductors are properly bridged or protected. Distribution boxes shall be provided with a disconnecting device for each branch circuit. Such disconnecting devices shall be equipped or designed in such a manner that it can be determined by visual observation when such a device is open and that the circuit is deenergized, and the distribution box shall be labeled to show which circuit each device controls. Trailing cable and power-cable connections to junction boxes shall not be made or broken under load. Power wires and cables shall be insulated adequately where they pass into or out of electrical compartments. Cables shall enter metal frames of motors, splice boxes, and electrical compartments only through proper fittings. When insulated wires, other than cables, pass through metal frames, the holes shall be substantially bushed with insulated bushings. Telephone and low-potential signal wire shall be protected, by isolation or suitable insulation, or both, from contacting energized power conductors or any other power source. High-potential electrical conductors shall be covered, insulated, or placed to prevent contact with low potential conductors. The potential on bare signal wires accessible to contact by persons shall not exceed 48 volts. Permanent splices and repairs made in power cables, including the ground conductor where provided, shall be— (a) Mechanically strong with electrical conductivity as near as possible to that of the original; (b) Insulated to a degree at least equal to that of the original, and sealed to exclude moisture; and, (c) Provided with damage protection as near as possible to that of the original, including good bonding to the outer jacket. Power cables energized to potentials in excess of 150 volts, phase-to-ground, shall not be moved with equipment unless sleds or slings, insulated from such equipment, are used. When such energized cables are moved manually, insulated hooks, tongs, ropes, or slings shall be used unless suitable protection for persons is provided by other means. This does not prohibit pulling or dragging of cable by the equipment it powers when the cable is physically attached to the equipment by suitable mechanical devices, and the cable is insulated from the equipment in conformance with other standards in this part. Electrically powered equipment shall be deenergized before mechanical work is done on such equipment. Power switches shall be locked out or other measures taken which shall prevent the equipment from being energized without the knowledge of the individuals working on it. Suitable warning notices shall be posted at the power switch and signed by the individuals who are to do the work. Such locks or preventive devices shall be removed only by the persons who installed them or by authorized personnel. Power circuits shall be deenergized before work is done on such circuits unless hot-line tools are used. Suitable warning signs shall be posted by the individuals who are to do the work. Switches shall be locked out or other measures taken which shall prevent the power circuits from being energized without the knowledge of the individuals working on them. Such locks, signs, or preventive devices shall be removed only by the person who installed them or by authorized personnel. Principal power switches shall be labeled to show which units they control, unless identification can be made readily by location. Where access is necessary, suitable clearance shall be provided at stationary electrical equipment or switchgear. Dry wooden platforms, insulating mats, or other electrically-nonconductive material shall be kept in place at all switchboards and power-control switches where shock hazards exist. However, metal plates on which a person normally would stand and which are kept at the same potential as the grounded, metal, non-current-carrying parts of the power switches to be operated may be used. Suitable danger signs shall be posted at all major electrical installations. Areas containing major electrical installations shall be entered only by authorized persons. Electrical connections and resistor grids that are difficult or impractical to insulate shall be guarded, unless protection is provided by location. All metal enclosing or encasing electrical circuits shall be grounded or provided with equivalent protection. This requirement does not apply to battery-operated equipment. Metal fencing and metal buildings enclosing transformers and switchgear shall be grounded. Frame grounding or equivalent protection shall be provided for mobile equipment powered through trailing cables. Continuity and resistance of grounding systems shall be tested immediately after installation, repair, and modification; and annually thereafter. A record of the resistance measured during the most recent test shall be made available on a request by the Secretary or his duly authorized representative. When a potentially dangerous condition is found it shall be corrected before equipment or wiring is energized. Inspection and cover plates on electrical equipment and junction boxes shall be kept in place at all times except during testing or repairs. Hand-held electric tools shall not be operated at high potential voltages. Portable extension lights, and other lights that by their location present a shock or burn hazard, shall be guarded. Lamp sockets shall be of a weatherproof type where they are exposed to weather or wet conditions that may interfere with illumination or create a shock hazard. Fuses shall not be removed or replaced by hand in an energized circuit, and they shall not otherwise be removed or replaced in an energized circuit unless equipment and techniques especially designed to prevent electrical shock are provided and used for such purpose. Fuse tongs or hotline tools, shall be used when fuses are removed or replaced in high-potential circuits. Trailing cables shall be attached to machines in a suitable manner to protect the cable from damage and to prevent strain on the electrical connections. Surplus trailing cables to shovels, cranes and similar equipment shall be— (a) Stored in cable boats; (b) Stored on reels mounted on the equipment; or (c) Otherwise protected from mechanical damage. Operating controls shall be installed so that they can be operated without danger of contact with energized conductors. Switches and starting boxes shall be of safe design and capacity. Both rails shall be bonded or welded at every joint and rails shall be crossbonded at least every 200 feet if the track serves as the return trolley circuit. When rails are moved, replaced, or broken bonds are discovered, they shall be rebonded within three working shifts. Overhead high-potential powerlines shall be installed as specified by the National Electrical Code. Guy wires of poles supporting high-voltage transmission lines shall meet the requirements for grounding or insulator protection of the National Electrical Safety Code, part 2, entitled “Safety Rules for the Installation and Maintenance of Electric Supply and Communication Lines” (also referred to as National Bureau of Standards Handbook 81, Nov. 1, 1961), and Supplement 2 thereof issued March 1968, which are hereby incorporated by reference and made a part hereof. These publications and documents may be obtained from the National Institute of Science and Technology, 100 Bureau Drive, Stop 3460, Gaithersburg, MD 20899–3460. Telephone: 301–975–6478 (not a toll free number); http://ts.nist.gov/nvl; or from the Government Printing Office, Information Dissemination (Superintendent of Documents), P.O. Box 371954, Pittsburgh, PA 15250–7954; Telephone: 866–512–1800 (toll free) or 202–512–1800; http://bookstore.gpo.gov, or may be examined in any Metal and Nonmetal Mine Safety and Health District Office of the Mine Safety and Health Administration. [53 FR 32526, Aug. 25, 1988, as amended at 60 FR 35695, July 11, 1995; 71 FR 16667, Apr. 3, 2006] Telegraph, telephone, or signal wires shall not be installed on the same crossarm with power conductors. When carried on poles supporting powerlines, they shall be installed as specified by the National Electrical Code. Trolley wires shall be installed at least seven feet above rails where height permits, and aligned and supported to suitably control sway and sag. Ground wires for lighting circuits powered from trolley wires shall be connected securely to the ground return circuit.
Title 30: Mineral Resources
PART 57—SAFETY AND HEALTH STANDARDS—UNDERGROUND METAL AND NONMETAL MINES
Subpart K—Electricity
Surface and Underground
§ 57.12001 Circuit overload protection.
§ 57.12002 Controls and switches.
§ 57.12003 Trailing cable overload protection.
§ 57.12004 Electrical conductors.
§ 57.12005 Protection of power conductors from mobile equipment.
§ 57.12006 Distribution boxes.
§ 57.12007 Junction box connection procedures.
§ 57.12008 Insulation and fittings for power wires and cables.
§ 57.12010 Isolation or insulation of communication conductors.
§ 57.12011 High-potential electrical conductors.
§ 57.12012 Bare signal wires.
§ 57.12013 Splices and repairs of power cables.
§ 57.12014 Handling energized power cables.
§ 57.12016 Work on electrically-powered equipment.
§ 57.12017 Work on power circuits.
§ 57.12018 Identification of power switches.
§ 57.12019 Access to stationary electrical equipment or switchgear.
§ 57.12020 Protection of persons at switchgear.
§ 57.12021 Danger signs.
§ 57.12022 Authorized persons at major electrical installations.
§ 57.12023 Guarding electrical connections and resistor grids.
§ 57.12025 Grounding circuit enclosures.
§ 57.12026 Grounding transformer and switchgear enclosures.
§ 57.12027 Grounding mobile equipment.
§ 57.12028 Testing grounding systems.
§ 57.12030 Correction of dangerous conditions.
§ 57.12032 Inspection and cover plates.
§ 57.12033 Hand-held electric tools.
§ 57.12034 Guarding around lights.
§ 57.12035 Weatherproof lamp sockets.
§ 57.12036 Fuse removal or replacement.
§ 57.12037 Fuses in high-potential circuits.
§ 57.12038 Attachment of trailing cables.
§ 57.12039 Protection of surplus trailing cables.
§ 57.12040 Installation of operating controls.
§ 57.12041 Design of switches and starting boxes.
§ 57.12042 Track bonding.
§ 57.12045 Overhead powerlines.
§ 57.12047 Guy wires.
§ 57.12048 Communication conductors on power poles.
§ 57.12050 Installation of trolley wires.
§ 57.12053 Circuits powered from trolley wires.
Surface Only
§ 57.12065 Short circuit and lightning protection.
Powerlines, including trolley wires, and telephone circuits shall be protected against short circuits and lightning.
§ 57.12066 Guarding trolley wires and bare powerlines.
Where metallic tools or equipment can come in contact with trolley wires or bare powerlines, the lines shall be guarded or deenergized.
§ 57.12067 Installation of transformers.
Transformers shall be totally enclosed, or shall be placed at least 8 feet above the ground, or installed in a transformer house, or surrounded by a substantial fence at least 6 feet high and at least 3 feet from any energized parts, casings, or wiring.
§ 57.12068 Locking transformer enclosures.
Transformer enclosures shall be kept locked against unauthorized entry.
§ 57.12069 Lightning protection for telephone wires and ungrounded conductors.
Each ungrounded conductor or telephone wire that leads underground and is directly exposed to lightning shall be equipped with suitable lightning arrestors of approved type within 100 feet of the point where the circuit enters the mine. Lightning arrestors shall be connected to a low resistance grounding medium on the surface and shall be separated from neutral grounds by a distance of not less than 25 feet.
§ 57.12071 Movement or operation of equipment near high-voltage powerlines.
When equipment must be moved or operated near energized high-voltage powerlines (other than trolley lines) and the clearance is less than 10 feet, the lines shall be deenergized or other precautionary measures shall be taken.
Underground Only
§ 57.12080 Bare conductor guards.
Trolley wires and bare power conductors shall be guarded at mantrip loading and unloading points, and at shaft stations. Where such trolley wires and bare power conductors are less than 7 feet above the rail, they shall be guarded at all points where persons work or pass regularly beneath.
§ 57.12081 Bonding metal pipelines to ground return circuits.
All metal pipelines, 1,000 feet or more in length running parallel to trolley tracks, that are used as a ground return circuit shall be bonded to the return circuit rail at the ends of the pipeline and at intervals not to exceed 500 feet.
§ 57.12082 Isolation of powerlines.
Powerlines shall be well separated or insulated from waterlines, telephone lines and air lines.
§ 57.12083 Support of power cables in shafts and boreholes.
Power cables in shafts and boreholes shall be fastened securely in such a manner as to prevent undue strain on the sheath, insulation, or conductors.
§ 57.12084 Branch circuit disconnecting devices.
Disconnecting switches that can be opened safely under load shall be provided underground at all branch circuits extending from primary power circuits near shafts, adits, levels and boreholes.
§ 57.12085 Transformer stations.
Transformer stations shall be enclosed to prevent persons from unintentionally or inadvertently contacting energized parts.
§ 57.12086 Location of trolley wire.
Trolley and trolley feeder wire shall be installed opposite the clearance side of haulageways. However, this standard does not apply where physical limitations would prevent the safe installation or use of such trolley and trolley feeder wire.
§ 57.12088 Splicing trailing cables.
No splice, except a vulcanized splice or its equivalent, shall be made in a trailing cable within 25 feet of the machine unless the machine is equipped with a cable reel or other power feed cable payout-retrieval system. However, a temporary splice may be made to move the equipment for repair.
Browse Previous | Browse Next

