33 C.F.R. § 149.413 On a manned deepwater port, what spaces require a fixed fire-extinguishing system?
Title 33 - Navigation and Navigable Waters
The manned deepwater port spaces or systems listed in paragraphs (a) through (c) of this section must be protected by an approved fixed-gaseous, or other approved fixed-type, extinguishing system. (a) Paint lockers of capacity in excess of 200 cubic feet and similar spaces containing flammable liquids. (b) Galley range or deep fat fryer. (c) Each enclosed space containing internal combustion or gas turbine machinery, with an aggregate power of more than 1,000 B.H.P., and any associated fuel oil units, purifiers, valves, or manifolds.
Title 33: Navigation and Navigable Waters
PART 149—DEEPWATER PORTS: DESIGN, CONSTRUCTION, AND EQUIPMENT
Subpart D—Firefighting and Fire-Protection Equipment
Firefighting Requirements
§ 149.413 On a manned deepwater port, what spaces require a fixed fire-extinguishing system?

