33 C.F.R. § 150.519   What are the requirements for emergency lighting and power systems?


Title 33 - Navigation and Navigable Waters


Title 33: Navigation and Navigable Waters
PART 150—DEEPWATER PORTS: OPERATIONS
Subpart F—Emergency and Specialty Equipment
Emergency Lighting and Power Systems


§ 150.519   What are the requirements for emergency lighting and power systems?

(a) The operator must test and inspect the emergency lighting and power systems at least once each week to determine if they are in proper operating condition. If they are not in proper operating condition, then the operator must repair or replace their defective parts.

(b) The operator must test under load each emergency generator driven by an internal combustion engine that is used for an emergency lighting and power system at least once in each month for a minimum of 2 hours.

(c) The operator must test each storage battery for the emergency lighting and power systems, at least once in each 6 months, to demonstrate the ability of the batteries to supply the emergency loads for an 8-hour period. The operator must follow the manufacturer's instructions in performing the battery test to ensure the batteries are not damaged during testing.