42 C.F.R. § 84.104   Gas tightness test; minimum requirements.


Title 42 - Public Health


Title 42: Public Health
PART 84—APPROVAL OF RESPIRATORY PROTECTIVE DEVICES
Subpart H—Self-Contained Breathing Apparatus

Browse Previous

§ 84.104   Gas tightness test; minimum requirements.

(a) Each apparatus will be tested for tightness by persons wearing it in an atmosphere of 1,000 p.p.m. isoamyl acetate.

(b) Six persons will each wear the apparatus in the test concentrations specified in paragraph (a) of this section for 2 minutes and none shall detect the odor or taste of the test vapor.