46 C.F.R. § 63.15-1 General.
Title 46 - Shipping
(a) Each automatic auxiliary boiler must be designed and constructed for its intended service according to the requirements of the parts referenced in §54.01–5, Table 54.01–5(A) of this chapter. (b) Controls and safety devices for automatic auxiliary boilers must meet the applicable requirements of ANSI/ASME CSD–1/CSD–1a, except Paragraph CG–310. (c) All devices and components of an automatic auxiliary boiler must satisfactorily operate within the marine environment. The boiler must satisfactorily operate with a momentary roll of 30°, a list of 15°, and a permanent trim of 5° with it installed in a position as specified by the manufacturer. (d) An electrical control used to shut down the automatic auxiliary boiler must be installed in accordance with §58.01–25 of this chapter. This device must stop the fuel supply to the fuel burning equipment. (e) Mercury tube actuated controls are prohibited from being installed and used on automatic auxiliary boilers.
Title 46: Shipping
PART 63—AUTOMATIC AUXILIARY BOILERS
Subpart 63.15—General Requirements
§ 63.15-1 General.