46 C.F.R. § 63.25-7   Exhaust gas boilers.


Title 46 - Shipping


Title 46: Shipping
PART 63—AUTOMATIC AUXILIARY BOILERS
Subpart 63.25—Requirements for Specific Types of Automatic Auxiliary Boilers

Browse Previous |  Browse Next

§ 63.25-7   Exhaust gas boilers.

(a) Construction. An auxiliary exhaust gas boiler must meet the applicable construction requirements of part 52 or part 53 of this chapter as determined from §54.01–5, Table 54.01–5(A) of this chapter.

(b) Controls. Each drum type exhaust gas steam boiler must have a feed water control system. The system must automatically supply the required amount of feed water and maintain it at the proper level. For boilers without a fixed water level, the control system must supply the feed water at a rate sufficient to ensure proper heat transfer. The system must adequately fill the boiler when cold.

(c) Alarms. When a condition arises which results in inadequate heat transfer, a high temperature alarm or low flow alarm must be activated. An audible alarm must automatically sound, and a visual indicator must indicate when the fluid temperature exceeds the maximum operating temperature or when the fluid/steam flowing through the heat exchanger is insufficient to ensure proper heat transfer. Additionally, an audible alarm must automatically sound, and a visual indicator must indicate when a soot fire is present in the exhaust gas boiler's uptake.