46 C.F.R. § 71.25-20   Fire-detecting and extinguishing equipment.


Title 46 - Shipping


Title 46: Shipping
PART 71—INSPECTION AND CERTIFICATION
Subpart 71.25—Annual Inspection

Browse Previous |  Browse Next

§ 71.25-20   Fire-detecting and extinguishing equipment.

(a) At each annual inspection, the inspector shall conduct the following tests and inspections of fire detecting and extinguishing equipment:

(1) All hand portable fire extinguishers and semiportable fire extinguishing systems shall be checked as noted in table 71.25–20(a)(1). In addition, the hand portable fire extinguishers and semiportable fire extinguishing systems shall be examined for excessive corrosion and general condition.

                          Table 71.25-20(a)(1)------------------------------------------------------------------------                Type unit                              Test------------------------------------------------------------------------Soda acid...............................  Discharge. Clean hose and                                           inside of extinguisher                                           thoroughly. Recharge.Foam....................................  Discharge. Clean hose and                                           inside of extinguisher                                           thoroughly. Recharge.Pump tank (water or antifreeze).........  Discharge. Clean hose and                                           inside of extinguisher                                           thoroughly. Recharge with                                           clean water or antifreeze.Cartridge operated (water, antifreeze or  Examine pressure cartirdge and loaded stream).                           replace if end is punctured                                           or if cartridge is otherwise                                           determined to have leaked or                                           to be in unsuitable                                           condition. Remove liquid.                                           Clean hose and inside of                                           extinguisher thoroughly.                                           Recharge with clean water,                                           solution or antifreeze.                                           Insert charged cartridge.Carbon Dioxide..........................  Weigh cylinders. Recharge if                                           weight loss exceed 10 percent                                           of weight of charge. Inspect                                           hose and nozzle to be sure                                           they are clear.\1\Dry chemical (cartridge-operated type)..  Examine pressure cartridge and                                           replace if end is punctured                                           or if cartridge is otherwise                                           determined to have leaked or                                           to be in unsuitable                                           condition. Inspect hose and                                           nozzle to see they are clear.                                           Insert charged cartridge. Be                                           sure dry chemical is free-                                           flowing (not caked) and                                           chamber contains full charge.Dry chemical (stored pressure type).....  See that pressure gage is in                                           operating range. If not, or                                           if seal is broken, weigh or                                           otherwise determine that full                                           charge of dry chemical is in                                           extinguisher. Recharge if                                           pressure is low or if dry                                           chemical is needed.Vaporizing liquid \2\ (pump type).......  Pump a few strokes into clean                                           pail and replace liquid. Keep                                           water out of extinguisher or                                           liquid. Keep extinguisher                                           completely full of liquid.Vaporizing liquid (stored pressure type)  See that pressure gage is in                                           operating range. Weigh or                                           check liquid level to                                           determine that full charge of                                           liquid is in extinguisher.                                           Recharge if pressure is low                                           or if liquid is needed.------------------------------------------------------------------------\1\ Cylinders must be tested and marked, and all flexible connections  and discharge hoses of semi-portable carbon dioxide and halon  extinguishers must be tested or renewed, as required by §§  147.60 and 147.65 of this chapter.\2\ Vaporizing-liquid type fire extinguishers containing carbon  tetrachloride or chlorobromomethane or other toxic vaporizing liquids  shall be removed from all vessels. (See § 76.50-5(e) of this  subchapter.)

(2) Fixed fire extinguishing systems shall be checked as noted in table 71.25–20(a)(2). In addition all parts of the fixed fire extinguishing systems shall be examined for excessive corrosion and general conditions.

                          Table 71.25-20(a)(2)------------------------------------------------------------------------              Type system                              Test------------------------------------------------------------------------Foam...................................  Systems utilizing a soda                                          solution shall have such                                          solution replaced. In all                                          cases, ascertain that powder                                          is not caked.Carbon dioxide.........................  Weigh cylinders. Recharge if                                          weight loss exceeds 10 percent                                          of weight of charge.\1\------------------------------------------------------------------------\1\ Cylinders must be tested and marked, and all flexible connections on  fixed carbon dioxide systems must be tested or renewed, as required by  §§ 147.60 and 147.65 of this chapter.

(3) All fire detecting and extinguishing systems, all piping controls, valves, and alarms shall be checked to ascertain that the system is in operating condition. In this respect, automatic sprinkling systems shall be checked by means of test stations or opening heads, smoke detecting systems shall be checked by introducing smoke into the accumulators, fire detecting and manual alarm systems shall be checked by test stations or actuating detectors or pull boxes, and steam smothering lines shall be checked with at least a 50 p.s.i. air pressure with the ends capped or by blowing steam through the lines at the designed pressure.

(4) The fire main system shall be operated and the pressure checked at the most remote and highest outlets. All fire hose shall be subjected to a test pressure equivalent to the maximum pressure to which they may be subjected in service, but not less than 100 p.s.i.

(b) [Reserved]

[CGFR 65–50, 30 FR 16895, Dec. 30, 1965, as amended by CGFR 68–32, 33 FR 5716, Apr. 12, 1968; CGD 84–044, 53 FR 7748, Mar. 10, 1988]