46 C.F.R. Subpart 105.30—Electrical Requirements
Title 46 - Shipping
(a) In compartments or areas containing tanks or pumps handling other than Grade E petroleum products, no electrical fittings, fixtures, nor electrical equipment shall be installed or used unless approved for a Class I, Group D hazardous location and so labeled by Underwriter's Laboratories, Inc., or other recognized laboratories. (See subpart 110.10 of subchapter J (Electrical Engineering) of this chapter for listings of standards.) (b) All electrical equipment, fixtures and fittings within 10 feet of a vent outlet or a dispensing outlet shall be explosion proof and shall be labeled as explosion proof by Underwriter's Laboratories, Inc., or other recognized laboratory, as suitable for Class I, Group D atmospheres. (a) All electrical equipment shall be grounded to the vessel's common ground.
Title 46: Shipping
PART 105—COMMERCIAL FISHING VESSELS DISPENSING PETROLEUM PRODUCTS
Subpart 105.30—Electrical Requirements
§ 105.30-1 Electrical fittings and fixtures.
§ 105.30-5 Grounding of electrical equipment.