§ 107.235   Servicing of hand portable fire extinguishers, semi-portable fire extinguishers and fixed fire-extinguishing systems.

(a) Each hand portable fire extinguisher and each semi-portable fire extinguisher on board the unit must be serviced as set out in Table 107.235 and examined for excessive corrosion and general condition.

                              Table 107.235------------------------------------------------------------------------       Type extinguisher               Test and servicing required------------------------------------------------------------------------Soda Acid......................  Discharge, clean hose and inside of                                  extinguisher thoroughly. Recharge.Foam...........................  Discharge, clean hose and inside of                                  extinguisher thoroughly. Recharge.Pump Tank (water or antifreeze)  Discharge, clean hose and inside of                                  extinguisher thoroughly. Recharge with                                  clean water or antifreeze.Cartridge operated (water,       Examine pressure cartridge and replace antifreeze or loaded stream).    if end is punctured or if cartridge is                                  otherwise determined to have leaked or                                  to be in unsuitable condition. Remove                                  liquid, clean hose and inside of                                  extinguisher thoroughly. Recharge with                                  clean water, solution, or antifreeze.                                  Insert charged cartridge.Carbon Dioxide.................  Weigh cylinders. Recharge if weight                                  loss exceeds 10 percent. Inspect hose                                  and nozzle to be sure they are clear.Dry chemical (cartridge-         Examine pressure cartridge and replace operated type).                  if end is punctured or if cartridge is                                  otherwise determined to have leaked or                                  to be in unsuitable condition. Inspect                                  hose and nozzle to see if they are                                  clear. Insert charged cartridge. Be                                  sure dry chemical is free-flowing (not                                  caked) and chamber contains full                                  charge.Dry chemical (stored pressure    See that pressure gage is in operating type).                           range. If not, or if seal is broken,                                  weigh or otherwise determine that full                                  charge of dry chemical is in                                  extinguisher. Recharge if pressure is                                  low or if dry chemical is needed.------------------------------------------------------------------------

(b) Each fixed fire-extinguishing system must be examined for excessive corrosion and general condition and be serviced by—

(1) Recharging the cylinders of each carbon dioxide system, if the weight loss is more than 10% of the weight of the charge;

(2) Testing each foam system, except premix systems by—

(i) Discharging foam for approximately 15 seconds from a nozzle designated by the marine inspector;

(ii) Discharging water from all other lines and nozzles; and

(iii) Taking a sample of the foam liquid and submitting it to the manufacturer or his authorized representative for determination of its specific gravity, PH, percentage of water dilution, and solid content, and certification as a suitable firefighting foam;

(3) Removing the pressure cartridge of each premix aqueous film forming foam system and replacing the cartridge if the seal is punctured, sampling the premix solution in accordance with the manufacturer's instructions, and replacing cylinders that are discharged.

Note: All carbon dioxide cylinders and discharge hoses of semi-portable carbon dioxide and halon extinguishers must be tested and marked in accordance with §§147.60 and 147.65 of this chapter.

[CGD 73–251, 43 FR 56802, Dec. 4, 1978, as amended by CGD 84–044, 53 FR 7749, Mar. 10, 1988]