46 C.F.R. § 108.411   Smoke detection system.


Title 46 - Shipping


Title 46: Shipping
PART 108—DESIGN AND EQUIPMENT
Subpart D—Fire Extinguishing Systems

Browse Previous |  Browse Next

§ 108.411   Smoke detection system.

Each smoke accumulator in a smoke detection system must be located on the overhead of the compartment protected by the system in a location—

(a) Where no portion of the overhead of the compartment is more than 12 meters (40 feet) from an accumulator;

(b) That is no closer to the opening of a ventilator than 3 times the diameter or equivalent size of the opening.

(c) Where damage to the accumulator is unlikely to occur if it is not protected.