46 C.F.R. § 111.05-31   Grounding conductors for systems.


Title 46 - Shipping


Title 46: Shipping
PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS
Subpart 111.05—Equipment Ground, Ground Detection, and Grounded Systems

Browse Previous |  Browse Next

§ 111.05-31   Grounding conductors for systems.

(a) A conductor for grounding a direct-current system must be the larger of:

(1) The largest conductor supplying the system; or

(2) No. 8 AWG (8.4mm2 ).

(b) A conductor for grounding the neutral of an alternating-current system must meet Table 111.05–31(b).

 Table 111.05-31(b)_Neutral Grounding Conductor for Alternating-Current                                 System------------------------------------------------------------------------ Size of the largest generator cable or equivalent      for parallel generators_AWG-MCM (mm\2\)        Size of the system---------------------------------------------------       grounding                                    Less than or    conductor_AWG(mm\2\)          Greater than                equal to------------------------------------------------------------------------                                 2 (33.6).........          8 (8.4)2 (33.6).......................  0 (53.5).........         6 (13.3)0 (53.5).......................  3/0 (85.0).......         4 (21.2)3/0 (85.0).....................  350 MCM (177)....         2 (33.6)350 MCM (177)..................  600 MCM (304)....         0 (53.5)600 MCM (304)..................  1100 MCM (557)...       2/0 (67.5)1100 MCM (557).................  .................       3/0 (85.0)------------------------------------------------------------------------

Browse Previous |  Browse Next

chanrobles.com