46 C.F.R. § 111.10-9   Ship's service supply transformers; two required.


Title 46 - Shipping


Title 46: Shipping
PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS
Subpart 111.10—Power Supply

Browse Previous

§ 111.10-9   Ship's service supply transformers; two required.

If transformers are used to supply the ship's service distribution system required by this subpart for ships and mobile offshore drilling units, there must be at least two installed, independent power transformers. With the largest transformer out of service, the capacity of the remaining units must be sufficient to supply the ship service loads.

Note to §111.10–9: A ship's service supply system would consist of transformers, overcurrent protection devices, and cables, and would normally be located in the system between a medium voltage bus and a low voltage ship's service switchboard.

[CGD 94–108, 61 FR 28277, June 4, 1996; 61 FR 33045, June 26, 1996]