46 C.F.R. § 111.12-9 Generator cables.
Title 46 - Shipping
(a) The current-carrying capacity of generator cables must not be: (1) Less than 115 percent of the continuous generator rating; or (2) Less than 115 percent of the overload for a machine with a 2 hour or greater overload rating. (b) Generator cables must not be in the bilges.
Title 46: Shipping
PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS
Subpart 111.12—Generator Construction and Circuits
§ 111.12-9 Generator cables.