46 C.F.R. § 111.30-19 Buses and wiring.
Title 46 - Shipping
(a) General. Each bus must meet the requirements of either— (1) Section 17.11 of IEEE Std 45; or (2) IEC 92–302 (clause 6). (b) Wiring. Instrumentation and control wiring must be— (1) Suitable for installation within in a switchboard enclosure and be rated at 90° C or higher; (2) Stranded copper; (3) No. 14 AWG (2.10 mm2 ) or larger or must be ribbon cable or similar conductor size cable recommended for use in low-power instrumentation, monitoring, or control circuits by the equipment manufacturer; (4) Flame retardant meeting ANSI/UL 1581 test VW–1 or IEC 332–1; and (5) Extra flexible, if used on a hinged panel. [CGD 94–108, 61 FR 28278, June 4, 1996, as amended at 62 FR 23908, May 1, 1997]
Title 46: Shipping
PART 111—ELECTRIC SYSTEMS—GENERAL REQUIREMENTS
Subpart 111.30—Switchboards
§ 111.30-19 Buses and wiring.