46 C.F.R. § 120.354 Battery installations.
Title 46 - Shipping
(a) Large batteries. Each large battery installation must be located in a locker, room or enclosed box solely dedicated to the storage of batteries. Ventilation must be provided in accordance with §111.15–10 in subchapter J of this chapter. Electrical equipment located within the battery enclosure must be approved by an independent laboratory for Class I, Division 1, Group B hazardous locations and meet §111.105 in subchapter J of this chapter. (b) Small batteries. Each small battery installation must be located in a well ventilated space and protected from falling objects. A small battery installation must not be in a closet, storeroom, or similar space.
Title 46: Shipping
PART 120—ELECTRICAL INSTALLATION
Subpart C—Power Sources and Distribution Systems
§ 120.354 Battery installations.