46 C.F.R. § 132.310   Fixed fire-extinguishing systems for paint lockers.


Title 46 - Shipping


Title 46: Shipping
PART 132—FIRE-PROTECTION EQUIPMENT
Subpart C—Miscellaneous

Browse Next

§ 132.310   Fixed fire-extinguishing systems for paint lockers.

(a) Except as provided by paragraph (b) of this section, a fixed gaseous fire-extinguishing system or another approved fixed fire-extinguishing system must be installed in each paint locker.

(b) No fixed fire-extinguishing system need be installed in a paint locker that is—

(1) Less than 1.7 cubic meters (60 cubic feet) in volume;

(2) Accessible only from the weather deck; and

(3) Not adjacent to a tank for flammable or combustible liquid.

(c) Each fixed fire-extinguishing system installed must comply with part 95 of this chapter or be approved by the Commanding Officer, Marine Safety Center.