46 C.F.R. § 153.312 Ventilation system standards.
Title 46 - Shipping
A cargo handling space ventilation system must meet the following: (a) A ventilation system exhaust duct must discharge no less than 10 m (approx. 32.8 ft) from openings into or ventilation intakes for, accommodation or service spaces. (b) A ventilation system must not recycle vapors from ventilation discharges. (c) Except for the space served by the ventilation duct, a ventilation duct must not pass through a machinery room, an accommodation space, or working spaces. (d) A ventilation system must be operable from outside the space it ventilates. (e) A ventilation system must be sized to change the air in the ventilated space at least 30 times per hour. (f) A ventilation system must not allow air to stagnate in any part of a ventilated space. (g) A ventilation system must be able to exhaust air from both above and below the deck plates of a ventilated space.
Title 46: Shipping
PART 153—SHIPS CARRYING BULK LIQUID, LIQUEFIED GAS, OR COMPRESSED GAS HAZARDOUS MATERIALS
Subpart B—Design and Equipment
Cargo Handling Space Ventilation
§ 153.312 Ventilation system standards.