49 C.F.R. § 192.359 Customer meter installations: Operating pressure.
Title 49 - Transportation
(a) A meter may not be used at a pressure that is more than 67 percent of the manufacturer's shell test pressure. (b) Each newly installed meter manufactured after November 12, 1970, must have been tested to a minimum of 10 p.s.i. (69 kPa) gage. (c) A rebuilt or repaired tinned steel case meter may not be used at a pressure that is more than 50 percent of the pressure used to test the meter after rebuilding or repairing. [35 FR 13257, Aug. 19, 1970, as amended by Amdt. 192–1, 35 FR 17660, Nov. 17, 1970; Amdt. 192–85, 63 FR 37503, July 13, 1998]
Title 49: Transportation
PART 192—TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS
Subpart H—Customer Meters, Service Regulators, and Service Lines
§ 192.359 Customer meter installations: Operating pressure.