10 C.F.R. § 431.110   Energy conservation standards and their effective dates.


Title 10 - Energy


Title 10: Energy
PART 431—ENERGY EFFICIENCY PROGRAM FOR CERTAIN COMMERCIAL AND INDUSTRIAL EQUIPMENT
Subpart G—Commercial Water Heaters, Hot Water Supply Boilers and Unfired Hot Water Storage Tanks
Energy Conservation Standards


§ 431.110   Energy conservation standards and their effective dates.

Each commercial storage water heater, instantaneous water heater, unfired hot water storage tank and hot water supply boiler1 must meet the applicable energy conservation standard level(s) as follows:

  

1 Any packaged boiler that provides service water, that meets the definition of “commercial packaged boiler” in subpart E of this part, but does not meet the definition of “ hot water supply boiler” in subpart G, must meet the requirements that apply to it under subpart E.

 ----------------------------------------------------------------------------------------------------------------                                                                   Energy conservation standard \a\ (products                                                                manufactured on and after October 29, 2003) \b\              Product                          Size           --------------------------------------------------                                                                    Minimum thermal        Maximum standby loss                                                                      efficiency                   \c\----------------------------------------------------------------------------------------------------------------Electric storage water heaters....  All......................  N/A.....................  0.30 + 27/Vm (%/hr)Gas-fired storage water heaters...  [le]155,000 Btu/hr.......  80%.....................  Q/800 + 110(Vr) 1/2                                    >155,000 Btu/hr.......  80%.....................   (Btu/hr)                                                                                         Q/800 + 110(Vr) 1/2                                                                                          (Btu/hr)Oil-fired storage water heaters...  [le]155,000 Btu/hr.......  78%.....................  Q/800 + 110(Vr) 1/2                                    >155,000 Btu/hr.......  78%.....................   (Btu/hr)                                                                                         Q/800 + 110(Vr) 1/2                                                                                          (Btu/hr)Gas-fired instantaneous water       <10 gal...............  80%.....................  N/A heaters and hot water supply       >=10 gal.................  80%.....................  Q/800 + 110(Vr) 1/2 boilers.                                                                                 (Btu/hr)Oil-fired instantaneous water       <10 gal...............  80%.....................  N/A heaters and hot water supply       >=10 gal.................  78%.....................  Q/800 + 110(Vr) 1/2 boilers.                                                                                 (Btu/hr)----------------------------------------------------------------------------------------------------------------
 ------------------------------------------------------------------------                                                       Minimum thermal           Product                     Size               insulation------------------------------------------------------------------------Unfired hot water storage      All.................  R-12.5 tank.------------------------------------------------------------------------\a\ Vm is the measured storage volume and Vr is the rated volume, both  in gallons. Q is the nameplate input rate in Btu/hr.\b\ For hot water supply boilers with a capacity of less than 10  gallons: (1) the standards are mandatory for products manufactured on  and after October 21, 2005, and (2) products manufactured prior to  that date, and on or after October 23, 2003, must meet either the  standards listed in this table or the applicable standards in Subpart  E of this Part for a ``commercial packaged boiler.''\c\ Water heaters and hot water supply boilers having more than 140  gallons of storage capacity need not meet the standby loss requirement  if (1) the tank surface area is thermally insulated to R-12.5 or more,  (2) a standing pilot light is not used and (3) for gas or oil-fired  storage water heaters, they have a fire damper or fan assisted  combustion.