Subpart C—Design Conditions

§ 434.301   Design criteria.

301.1  The following design parameters shall be used for calculations required under subpart D of this part.

301.1.1  Exterior Design Conditions. Exterior Design Conditions shall be expressed in accordance with Table 301.1.

                 Table 301.1_Exterior Design Conditions------------------------------------------------------------------------ ------------------------------------------------------------------------Winter Design Dry-Bulb (99%)....  ..................  Degrees F.Summer Design Dry-Bulb (2.5%)...  ..................  Degrees F.Mean Coincident Wet-Bulb (2.5%).  ..................  Degrees F.Degree-Days, Heating (Base 65)..  ..................  HDD Base 65°                                                       F.Degree-Days, Cooling (Base 65)..  ..................  CDD Base 65°F.Annual Operting Hours, 8 a.m. to  ..................  Hours. 4 p.m. when 55°F[le]T[le]69°F.------------------------------------------------------------------------[The exterior design conditions shall be added to Table 301.1 from the  city-specific Shading Coefficient table from Appendix A of RS-1  (incorporated by reference, see § 434.701). Copies of specific  tables contained in Appendix A of RS-1 (incorporated by reference, see  § 434.701). can be obtained from the Energy Code for Federal  Commercial Buildings, Docket No. EE-RM-79-112-C, EE-43, Office of  Building Research and Standards, U.S. Department of Energy, Room 1J-  018, 1000 Independence Avenue, SW., Washington, DC 20585, (202) 586-  9127. Adjustments may be made to reflect local climates which differ  from the tabulated temperatures or local weather experience as  determined by the building official. Where local building site  climatic data are not available, climate data from a nearby location  included in RS-1, Appendix C, (incorporated by reference, see §  434.701) and RS-4 Chapter 24, Table 1, (incorporated by reference, see  § 434.701) shall be used as determined by the building official.]

301.2 Indoor Design Conditions. Indoor design temperature and humidity conditions shall be in accordance with the comfort criteria in RS–2 (incorporated by reference, see §434.701), except that humidification and dehumidification are not required.

Browse Previous |  Browse Next









































































chanrobles.com