§ 434.517   HVAC systems and equipment.

517.1  The specifications and requirements for the HVAC systems of the Prototype and Reference Buildings shall be those in Table 517.1.1, HVAC Systems for Prototype and Reference Buildings. For the calculation of the Design Energy Consumption, the HVAC systems and equipment of the Proposed Design shall be used.

517.2  The systems and types of energy presented in Table 517.1.1 are assumptions for calculating the Energy Cost Budget. They are not requirements for either systems or the type of energy to be used in the Proposed Building or for the calculation of the Design Energy Cost.

  Table 517.1.1_HVAC Systems of Prototype and Reference Buildings \1,2\------------------------------------------------------------------------                               System No.  (Table     Remarks  (Table   Building/space occupancy         517.4.1)              517.4.1)------------------------------------------------------------------------Assembly:    a. Churches (any size)...                  1    b. [le]50,000 ft \2\ or               1 or 3   Note 1.     [le]3 floors.    c. >50,000 ft \2\ or                    3     >3 floors.Office:    a. [le]20,000 ft \2\.....                  1    b. [le]50,000 ft \2\ and                   4     either [le]3 floors or     [le]75,000 ft \2\.    c. <75,000 ft \2\ or                    5     >3 floors.Retail:    a. [le]50,000 ft \2\.....             1 or 3   Note 1.    b. >50,000 ft \2\.....             4 or 5   Note 1.Warehouse....................                  1   Note 1.School:    a. [le]75,000 ft \2\ or                    1     [le]3 floors.    b. >75,000 ft \2\ or                    3     >3 floors.Hotel/Motel:    a. [le]3 stories.........             2 or 7   Note 5, 7.    b. >3 stories.........                  6   Note 6.Restaurant...................             1 or 3   Note 1.Health:    a. Nursing Home (any                  2 or 7   Note 7.     size).    b. [le]15,000 ft \2\.....                  1    c. <15,000 ft \2\ or                    4   Note 2.     [le]50,000 ft \2\.    d. >50,000 ft \2\.....                  5   Note 2, 3.Multi-family High Rise                        7 Residential >3 stories.------------------------------------------------------------------------\1\ Space and Service Water Heating budget calculations shall be made  using both electricity and natural gas. The Energy Cost Budget shall  be the lower of these two calculations. If natural gas is not  available at the rate, electricity and #2 fuel oil shall be used for  the budget calculations.\2\ The system and energy types presented in this Table are not intended  as requirements or recommendations for the proposed design. Floor  areas below are the total conditioned floor areas for the listed  occupancy type in the building. The number of floors indicated below  is the total number of occupied floors for the listed occupancy type.

517.3  HVAC Zones. HVAC zones for calculating the Energy Cost Budget of the Prototype or Reference Building shall consist of at least four perimeter and one interior zones per floor. Prototype Buildings shall have one perimeter zone facing each cardinal direction. The perimeter zones of Prototype and Reference Buildings shall be 15 ft in width, or one-third the narrow dimension of the building, when this dimension is between 30 ft and 45 ft inclusive, or one-half the narrow dimension of the building when this dimension is less than 30 ft. Zoning requirements shall be a default assumption for calculating the Energy Cost Budget. For multi-family high-rise residential buildings, the prototype building shall have one zone per dwelling unit. The proposed design shall have one zone per unit unless zonal thermostatic controls are provided within units; in this case, two zones per unit shall be modeled. Building types such as assembly or warehouse may be modeled as a single zone if there is only one space.

517.4  For calculating the Design Energy Consumption, no fewer zones shall be used than were in the Prototype and Reference Buildings. The zones in the simulation shall correspond to the zones provided by the controls in the Proposed Design. Thermally similar zones, such as those facing one orientation on different floors, may be grouped together for the purposes of either the Design Energy Consumption or Energy Cost Budget simulation.

                Table 517.4.1_HVAC System Description for Prototype and Reference Buildings \1,2\----------------------------------------------------------------------------------------------------------------         HVAC component                System #1           System #2           System #3           System #4----------------------------------------------------------------------------------------------------------------System Description..............  Packaged rooftop    Packaged terminal   Air handler per     Packaged rooftop                                   single room, one    air conditioner     zone with central   VAV w/perimeter                                   unit per zone.      with space heater   plant.              reheat.                                                       or heat pump, one                                                       heating/cooling                                                       unit per zone.Fan system_Design supply          Note 9............  Note 10...........  Note 9............  Note 9. circulation rate.Supply fan total static pressure  1.3 in. W.C.......  N/A...............  2.0 in. W.C.......  3.0 in. W.C.Combined supply fan, motor, and   40%...............  N/A...............  50%...............  45%. drive efficiency.Supply fan control..............  Constant volume...  Fan Cycles with     Constant volume...  VAV w/forward                                                       call for heating                        curved                                                       or cooling.                             contrifugal fan                                                                                               and variable                                                                                               inlet vanes.Return fan total static pressure  N/A...............  N/A...............  0.6 in. W.C.......  0.6 in. W.C.Combined return fan, motor, and   N/A...............  N/A...............  25%...............  25%. drive efficiency.Return fan control..............  N/A...............  N/A...............  Constant volume...  VAV w/forward                                                                                               curved                                                                                               centrifugal fan                                                                                               and discharge                                                                                               dampers.Cooling System..................  Direct expansion    Direct expansion    Chilled water       Direct expansion                                   air cooled.         air cooled.         (Note 1).           air cooled.Heating System..................  Furnace, heat       Heat pump w/        Hot water (Note 8,  Hot water (Note                                   pump, or electric   electric            12).                12) or electric                                   resistance (Note    resistance                              resistance (Note                                   8).                 auxiliary or air                        B).                                                       conditioner w/                                                       space heater                                                       (Note 8).Remarks.........................  Dry bulb            No economizer.....  Dry bulb            Dry bulb                                   economizer per                          economizer per      economizer per                                   Section 7.4.3                           Section 434.514.    Section 434.514.                                   (barometric                                                 Minimum VAV                                   relief).                                                    setting per                                                                                               434.514 exception                                                                                               1. Supply air                                                                                               reset by zone of                                                                                               greatest cooling                                                                                               demand.----------------------------------------------------------------------------------------------------------------\1\ The systems and energy types presented in this Table are not intended as requirements or recommendations for  the proposed design.\2\ For numbered notes see end of Table 517.4.1.
                 Table 517.4.1_HVAC System Description for Prototype and Reference Buildings \1\----------------------------------------------------------------------------------------------------------------            HVAC component                    Systems #5               System #6                System #7----------------------------------------------------------------------------------------------------------------System Description...................  Built-up central VAV     Fourpipe fan coil per    Water source heat pump                                        with perimeter reheat.   zone with central                                                                 plant.Fan system_Design supply circulation   Note 9.................  Note 9.................  Note 10. rate.Supply fan total static pressure.....  4.0 in W.C.............  0.5 in W.C.............  0.5 in. W.C.Combined supply fan, motor, and drive  55%....................  25A....................  25%. efficiency.Supply fan control...................  VAV w/air-foil           Fan Cycles with call     Fan cycles w/call for                                        centrifugal fan and AC   for heating or cooling.  heating or cooling.                                        frequency variable                                        speed drive.Return fan total static pressure.....  1.0 in W.C.............  N/A....................  N/A.Combined return fan, motor, and drive  30%....................  N/A....................  N/A. efficiency.Return fan control...................  VAV with air-foil        N/A....................  N/A.                                        centrifugal fan and AC                                        frequency variable                                        speed drive.Cooling System.......................  Chilled water (Note 11)  Chilled water (Note 11)  Closed circuit,                                                                                          centrifugal blower                                                                                          type cooling tower                                                                                          sized per Note 11.                                                                                          Circulating pump sized                                                                                          for 2.7 GPM per ton.Heating System.......................  Hot water (Note 12) or   Hot water (Note 12) or   Electric or natural                                        electric resistance      electric resistance      draft fossil fuel                                        (Note 8).                (Note 8).                boiler (Note 8).Remarks..............................  Dry bulb economizer per  No economizer..........  Tower fans and boiler                                        Section 7.4.3. Minimum                            cycled to maintain                                        VAV setting per                                   circulating water                                        Section 7.4.4.3.                                  temperature between 60                                        Supply air reset by                               and design tower                                        zone of greatest                                  leaving water                                        cooling demand.                                   temperature.----------------------------------------------------------------------------------------------------------------

Numbered Notes for Table 517.4.1

HVAC System Descriptions for Prototype and Reference Buildings

Notes:

1. For occupancies such as restaurants, assembly and retail which are part of a mixed use building which, according to Table 517.4.1, includes a central chilled water plant (systems 3, 5, or 6), chilled water system type 3 or 5, as indicated in the Table, shall be used.

2. Constant volume may be used in zones where pressurization relationships must be maintained by code. VAV shall be used in all other areas, in accordance with §517.4

3. Provide run-around heat recovery systems for all fan systems with minimum outside air intake greater than 75%. Recovery effectiveness shall be 0.60.

4. If a warehouse is not intended to be mechanically cooled, both the Energy Cost Budgets and Design Energy Costs, may be calculated assuming no mechanical cooling.

5. The system listed is for guest rooms only. Areas such as public areas and back-of-house areas shall be served by system 4. Other areas such as offices and retail shall be served by the systems listed in Table 517.4.1 for those occupancy types.

6. The system listed is for guest rooms only. Areas such as public areas and back-of-house areas shall be served by System 5. Other areas such as offices and retail shall be served by the systems listed in Table 517.4.1.1 for those occupancy types.

7. System 2 shall be used for Energy Cost Budget calculation except in areas with design heating outside air temperatures less than 10°F.

8. Prototype energy budget cost calculations shall be made using both electricity and natural gas. If natural gas is not available at the site, electricity and #2 fuel oil shall be used. The Energy Cost Budget shall be the lower of these results. Alternatively, the Energy Cost Budget may be based on the fuel source that minimizes total operating, maintenance, equipment, and installation costs for the prototype over the building lifetime. Equipment and installation cost estimates shall be prepared using professionally recognized cost estimating tools, guides, and techniques. The methods of analysis shall conform to those of Subpart A of 10 CFR part 436. Energy costs shall be based on actual costs to the building as defined in this Section.

9. Design supply air circulation rate shall be based on a supply air to room air temperature differences of 20°F. A higher supply air temperature may be used if required to maintain a minimum circulation rate of 4.5 air changes per hour or 15 cfm per person at design conditions to each zone served by the system. If return fans are specified, they shall be sized from the supply fan capacity less the required minimum ventilation with outside air, or 75% or the supply air capacity, whichever is larger. Except where noted, supply and return fans shall be operated continually during occupied hours.

10. Fan System Energy when included in the efficiency rating of the unit as defined in §403.2.4.3 need not be modeled explicitly for this system. The fan shall cycle with calls for heating or cooling.

11. Chilled water systems shall be modeled using a reciprocating chiller for systems with total cooling capacities less than 175 tons, and centrifugal chillers for systems with cooling capacities of 175 tons or greater. For systems with cooling or 600 ton or more, the Energy Cost Budget shall be calculated using two centrifugal chillers lead/lag controlled. Chilled water pumps shall be sized using a 12°F temperature rise, from 44°F to 56°F operating at 65 feed of head and 65% combined impeller and motor efficiency. Condenser water pumps shall be sized using a 10°F temperature rise, operating at 60 feet of head and 60% combined impeller and motor efficiency. The cooling tower shall be an open circuit, centrifugal blower type sized for the larger of 85°F leaving water temperature or 10°F approach to design wet bulb temperature. The tower shall be controlled to provide a 65°F leaving water temperature whenever weather conditions permit, floating up to design leaving water temperature at design conditions. Chilled water supply temperature shall be reset in accordance with §434.518.

12. Hot water system shall include a natural draft fossil fuel or electric boiler per Note 8. The hot water pump shall be sized based on a 30°F temperature drop, for 18°F to 150°F, operating at 60 feet of head and a combined impeller and motor efficiency of 60%. Hot water supply temperature shall be reset in accordance with §434.518.

517.5  Equipment Sizing and Redundant Equipment. For calculating the Energy Cost Budget of Prototype or Reference Buildings, HVAC equipment shall be sized to meet the requirements of subsection 403.2.2, without using any of the exceptions. The size of equipment shall be that required for the building without process loads considered. Redundant or emergency equipment need not be simulated if it is controlled so that it will not be operated during normal operations of the building. The designer shall document the installation of process equipment and the size of process loads.

517.6  For calculating the Design Energy Consumption, actual air flow rates and installed equipment size shall be used in the simulation, except that excess capacity provided to meet process loads need not be modeled unless the process load was not modeled in setting Energy Cost Budget. Equipment sizing in the simulation of the Proposed Design shall correspond to the equipment actually selected for the design and the designer shall not use equipment sized automatically by the simulation tool.

517.6.1  Redundant or emergency equipment need not be simulated if it is controlled to not be operated during normal operations of the building.