46 C.F.R. § 154.805 Vent masts.
Title 46 - Shipping
Relief valves or common vent headers from relief valves must discharge to a vent mast that: (a) Discharges vertically upward; (b) Has a rain cap or other means of preventing the entrance of rain or snow; (c) Has a screen with 25mm (1 inch) wire mesh or bars not more than 25mm (1 in.) apart on the discharge port; (d) Extends at least to a height of B/3 or 6m (19.7 ft.), whichever is greater, above the weather deck and 6m (19.7 ft.) above the working level; (e) For a cargo tank, does not exhaust cargo vapors within a radius of B or 25m (82 ft.), whichever is less, from any forced or natural ventilation intake or other opening to an accommodation, service, control station, or other gas-safe space, except that for vessels less than 90m (295 ft.) in length, shorter distances may be specially approved by the Commandant (G-MSO); (f) For a containment system, except a cargo tank, does not exhaust vapor within a radius of 10m (32.8 ft.) or less from any forced or natural ventilation intake or other opening to an accommodation, service, control station, or other gas-safe space; (g) Has drains to remove any liquid that may accumulate; and (h) Prevents accumulations of liquid at the relief valves. [CGD 74–289, 44 FR 26009, May 3, 1979, as amended by CGD 82–063b, 48 FR 4782, Feb. 3, 1983]
Title 46: Shipping
PART 154—SAFETY STANDARDS FOR SELF-PROPELLED VESSELS CARRYING BULK LIQUEFIED GASES
Subpart C—Design, Construction and Equipment
Cargo Vent Systems
§ 154.805 Vent masts.